Cabinet for DC-UPS J.Schneider AKKUTEC 2403C Vds (EN54-4)
Features:
J. Schneider Elektrotechnik cabinet DC-UPS 24V 3AJ
The battery buffered DC power supply is working according the stand-by parallel mode and ensures in connection with a lead-acid accumulator a safe continuous DC power supply during a determined time interval in case of mains failure. The total output current is shared between supply of the loads and charging of the batteries.
Technical Data | |
Nominal input voltage | 110/230VAC (±15%) |
Input voltage range for charging operation | 93.5V … 264.5V |
Nominal frequency | 47Hz … 63Hz |
Power consumption | 90VA |
Self current consumption | 100mA@24V |
Max. nominal input current | 0.5A |
Max. inrush current | 35A/2ms |
Max. nominal output current | 3A |
Nominal output voltage (in mains operation) | 24VDC |
Output voltage range (with temperature tracking) | 26.4V … 28.6VDC ±0.4% |
Charging characteristics | I/U DIN41773 |
Charging end voltage without temp.-Sensor | 26.4VDC ±0.4% |
Deep discharge protection and load shedding | 20.4VDC ±0.4% |
Max power loss ‚worst-case‘ | 14W |
Efficiency | 85% q (Ue=230V; Ua=26.4VDC; Ia=INenn) |
Voltage ripple | < 100mV eff. |
Internal device protection | 2A (T), 250V |
Fuse DC-output circuit (external) | 5A(T) |
Fuse DC-battery circuit (external) | 5A(T) |
potential-free relay-contact | |
Max. signal contact load (Bat-OK1) | 30V/ 0.5A |
potential-free relay-contact | |
Max. signal contact load (General fault 1) | 30V/ 0.5A |
potential-free relay-contact | |
Max. signal voltage range (Shut-Down) | 24VDC (6-45VDC) |
floating switching input | |
Accumulator type | Pb-accumulator, maintenance-free |
max 2x26Ah | |
Back-up time | Accumulator specific |
Protective system | IP30 |
Operating temperature | -10°C … 50°C |
Storage temperature | -10°C … 50°C |
Rel. humidity | ≤95% no condensation |
Max. installation altitude | 2000m above sea level |
Dimensions (HxWxD) | 362mm, 464mm, 145mm |
Weight | 7,5Kg |